Design features:
Top- or bottom-supported, one or two drum designs; proven attractive in retrofit applications and also provides an option to reduce SO2 and NOx emissions; burns wet wood-based fuels other technologies can not combust (between approximately 2800 and 3500 Btu/lb HHV without support fuels); reduces sludge volume while producing steam.
Capacity new units:
- Bottom-supported: up to 225,000 lb/h (28.4 kg/s)
- Top-supported: from 225,000 to 700,000 lb/h (28.4 to 88.2 kg/s)
Capacity retrofits:
Up to 1,000,000 lb/h (126 kg/s)
Steam pressure:
To 2400 psig (16.5 MPa).
|
|
Superheater outlet temperature:
As required, up to 950F (510C).
Fuels:
Able to burn a wide range of conventional fuels and waste fuels with high moisture, including:
- Wood waste and bark
- Paper mill sludges
- Recycled paper facility sludges
- Sewage sludge
- Tire derived fuel
- Oil and natural gas
- Coal
|
|
For more information, please contact us.