The Burner Management System (BMS) is the safety and sequencing system used when firing boilers.
The BMS common logic includes fan control, power monitoring, boiler purge, boiler trip, firing permissive and furnace implosion/explosion protection. The fuel portion of the logic includes fuel headers and/or coal distribution systems, igniter control, burner control and air register control. When required, the BMS also includes the PA duct heaters and fuel lean gas reburn (FLGR) systems. Additional features that are available include automatic fan run-up, automatic coal mill start-up and shut-down sequencing, and automatic burner start/stop for load varying boilers.
Some standard features of FPS's BMS include a fully redundant, hard-wired Master Fuel Trip circuit, which is in full accordance with the latest NFPA 85 code. First out and "cause of trip" annunciation, alarming, and sequence of events monitoring are also included with each system.
We are one of a very few companies that can supply a BMS with a full complement of boiler safety products. Our safety systems can be supplied with control cabinets, flame scanners, igniters, valve trains, blower assemblies, and water level detectors - all of which are designed, built and tested in our factory. We also can handle installation, check-out, factory simulation and start-up.
For more information, please contact us.